Experimental studies of a typical sprinkler piping system in hospitals

Authors

  • Zhen-Yu Lin National Center for Research on Earthquake Engineering, Taipei, China
  • Fan-Ru Lin National Center for Research on Earthquake Engineering, Taipei, China
  • Juin-Fu Chai National Center for Research on Earthquake Engineering, Taipei, China
  • Kuo-Chun Chang National Center for Research on Earthquake Engineering, Taipei, China

DOI:

https://doi.org/10.5459/bnzsee.49.1.1-12

Abstract

Based on the issue of life safety and immediate needs of emergency medical services provided by hospitals after strong earthquakes, this paper aims to introduce a research programme on assessment and improvement strategies for a typical configuration of sprinkler piping systems in hospitals. The study involved component tests and subsystem tests. Cyclic loading tests were conducted to investigate the inelastic behaviour of components including concrete anchorages, screwed fittings of small-bore pipes and couplings. Parts of a horizontal piping system of a seismic damaged sprinkler piping system were tested using shaking table tests. Furthermore, horizontal piping subsystems with seismic resistant devices such as braces, flexible pipes and couplings were also tested.

The test results showed that the main cause of damage was the poor capacity of a screwed fitting of the small-bore tee branch. The optimum improvement strategy to achieve a higher nonstructural performance level for the horizontal piping subsystem is to strengthen the main pipe with braces and decrease moment demands on the tee branch by the use of flexible pipes. The hysteresis loops and failure modes of components were further discussed and will be used to conduct numerical analysis of sprinkler piping systems in future studies.

References

G & E Engineering Systems Inc (2009). “Fragility of Non-Structural Components: A.1 Fire Sprinkler Systems”. FEMA P-58/BD-3.9.12.

Huang CJ (2003). “A Study on the Earthquake Performance of Fire Sprinkler Systems”. Unpublished MD Thesis, Department of Architecture, National Cheng Kung University, [in Chinese].

Chai JF et. al. (2010). “Reconnaissance Report on Jiaxian Earthquake in Kaohsiung”. NCREE Report 10-010, Taipei, [in Chinese].

National Fire Protection Association (2010). “Standard for the Installation of Sprinkler Systems”. NFPA 13.

Hu PW and Chang KC (2015). “Seismic Fragility Analysis of Fire Protection Sprinkler Piping Seismic in Hospital”. MD Thesis, Department of Civil Engineering, National Taiwan University, [in Chinese].

Yuan Tian, Andre Filiatrault and Gilberto Mosqueda (2014). “Experimental Seismic Fragility of Pressurized Fire Suppression Sprinkler Piping Joints.” Earthquake Spectra, Vol 30, No. 4: pp. 1733-1748 DOI: https://doi.org/10.1193/111011EQS278M

Soroushian S, Zaghi AE, Maragakis M, Echevarria A, Tian Y and Filiatrault A (2015). “Analytical Seismic Fragility Analyses of Fire Sprinkler Piping System with Threaded Joints”. Earthquake Spectra, 32(2): 1125-1155. DOI: https://doi.org/10.1193/083112EQS277M

Huang JG (2012). “A Study on Seismic Behavior of Joints of Fire Protection Sprinkler Piping Systems in Hospitals”. Unpublished MD Thesis, Department of Civil Engineering, National Taiwan University, [in Chinese].

Kuo KC, Lin ZY, Chiang HW, Lin PY, Lin FR and Chai JF (2012). “Experimental Evaluation of the Seismic Performance Hospital Sprinkler Systems”. Proceedings of the 15th World Conference on Earthquake Engineering, Lisbon.

American Society of Civil Engineers (2010). “Minimum Design Loads for Buildings and Other Structures”. ASCE/SEI 7-10.

FM Approval LLC (2007). “Approval Standard for Pipe Couplings and Fittings for Aboveground Fire Protection System”. FM 1920.

American Concrete Institute (2007). “Qualification of Post-Installed Mechanical Anchors in Concrete and Commentary”. ACI 355.2-07, Detroit.

Ministry of the Interior (2011). “Seismic Design Specifications and Commentary of Buildings”. [in Chinese].

Downloads

Published

31-03-2016

How to Cite

Lin, Z.-Y., Lin, F.-R., Chai, J.-F., & Chang, K.-C. (2016). Experimental studies of a typical sprinkler piping system in hospitals. Bulletin of the New Zealand Society for Earthquake Engineering, 49(1), 1–12. https://doi.org/10.5459/bnzsee.49.1.1-12